Simulation Analysis of Transmission-Line Impedance Transformers for Petawatt-Class Pulsed Power Accelerators
-
Graphical Abstract
-
Abstract
Based on the transmission line code TLCODE, a 1-D circuit model for a transmission-line impedance transformer was developed and the simulation results were compared with those in the literature. The model was used to quantify the efficiencies of voltage-transport, energy-transport and power-transport for a transmission-line impedance transformer as functions of Ψ (the ratio of the output impedance to the input impedance of the transformer) and Γ (the ratio of the pulse width to the one-way transit time of the transformer) under a large scale of m (the coefficient of the generalized exponential impedance profile). Simulation results suggest that with the increase in Γ, from 0 to ∞, the power transport efficiency first increases and then decreases. The maximum power transport efficiency can reach 90% or even higher for an exponential impedance profile (m=1). With a consideration of dissipative loss in the dielectric and electrodes of the transformer, two representative designs of the water-insulated transformer are investigated for the next generation of petawatt-class z-pinch drivers. It is found that the dissipative losse in the electrodes is negligibly small, below 0.1%, but the dissipative loss in the water dielectric is about 1% to 4%.
-
-