Advanced Search+
YAN Jing (闫静), LIU Zhiyuan (刘志远), GENG Yingsan (耿英三), ZHANG Sheng (张胜), ZHANG Yingyao (张颖瑶). Investigation on X-Radiation for 126 kV Vacuum Interrupters[J]. Plasma Science and Technology, 2016, 18(5): 577-582. DOI: 10.1088/1009-0630/18/5/22
Citation: YAN Jing (闫静), LIU Zhiyuan (刘志远), GENG Yingsan (耿英三), ZHANG Sheng (张胜), ZHANG Yingyao (张颖瑶). Investigation on X-Radiation for 126 kV Vacuum Interrupters[J]. Plasma Science and Technology, 2016, 18(5): 577-582. DOI: 10.1088/1009-0630/18/5/22

Investigation on X-Radiation for 126 kV Vacuum Interrupters

Funds: supported by National Key Basic Research Program of China (973 Program) (No. 2015CB251002)
More Information
  • Received Date: September 08, 2015
  • When subjected to high voltages between opened contacts, vacuum interrupters may emit X-rays. In order to ensure that these are of an acceptable level, vacuum interrupters should comply with the limits for X-ray emission and the test procedures to be carried out to verify this based on relevant standards and specifications. In this paper, a comprehensive experimental study has been performed for 126 kV vacuum interrupters used in a transmission system to understand the X-radiation level and its influence by three main parameters, namely applied power-frequency voltage, contact gap and power-frequency voltage conditioning. The radiation instrument is an FJ347 radiometer and the X-radiation dose was measured at the power-frequency test voltage. These tests demonstrated that the X-radiation emission level for a 126 kV vacuum interrupter did not exceed the following: 5 μSv per hour at a rated voltage of 126 kV and 150 μSv per hour at a power-frequency voltage of 230 kV at 1 m distance. The X-radiation dose increased with the applied power-frequency voltage increasing and decreased with the contact gap increasing. The X-radiation dose for 126 kV vacuum interrupters decreased by 57% after the conditioning procedure with a certain power-frequency voltage. During the conditioning procedure, the average value of the X-radiation dose was 4.49 mSv, which means if a professional conditions 180 interrupters per year, it will be safe at the 6.4 m distance.
  • 1 Garzon R D. 2002, High Voltage Circuit Breaker Design and Applications (2nd Edition), Marcel Dekker Inc., New York 2 Greenwood A. 1994, Vacuum Switchgear. The Institution of Electrical Engineers, London 3 Matsui Y, Nagatake K, Takeshita M, et al. 2006, Development and technology of high voltage VCBs: Brief history and state of art. XXIInd International Symposium on Discharges and Electrical Insulation in Vacuum, Matsue, Japan 4 Homma M, Sakaki M, Kaneko E, et al. 2006, IEEE Trans. Dielectrics and Electrical Insulation, 13: 85 5 Wang J, Wang J. 2000, Review of theoretical research in vacuum arc and their applications in China. XIXth International Symposium on Discharges and Electrical Insulation in Vacuum, Xi’an, China 6 Liu Z, Wang J, Xiu S, et al. 2007, IEEE Trans. Plasma Sci., 35: 856 7 Slade P G. 2007, The Vacuum Interrupter: Theory,Design, and Application. CRC Press Taylor & Francis Group, Boca Raton 8 IEC 62271-1. 2007, High-Voltage Switchgear and Controlgear-part1: Common Specifications. IEC Pulication 9 ANSI C37.85. 1989, Alternating-current high-voltage power vacuum interrupters-safety requirements for Xradiation limits. American National Standard 10 Renz R, Gentsch D. 2010, Permissible X-ray radiation emitted by vacuum interrupters/devices at rated operating conditions. XXIVth International Symposium on Discharges and Electrical Insulation in Vacuum,Braunschweig, Germany 11 Council Directive 96/29. 1996, Euratom Basic safety standards for the protection of the health of workers and the general public against the dangers arising from ionising radiation 12 Li W, Guo Y, Wang C, et al. 2007, High Voltage Engineering, 33: 101 (in Chinese) 13 GB18871-2002. 2002, Basic Standards for Protection against Ionizing Radiation and for the Safety of Radiation Sources. Standards Press of China, Beijing (in Chinese) 14 Boxman R L, Sanders D M, Martin P J. 1995, Handbook of Vacuum Arc Science and Technology: Fundamentals and Applications. Noyes Publications, New Jersey